11.4: Velocity Loop Setup and Tuning
Initial velocity loop proportional gain (Vp) and velocity loop integral gain (Vi) values can be
calculated with The Calculate Function (p. 54).
Enter basic Velocity Loop settings
Click V Loop (screen contents vary with model and configuration):
Note: For Plus products the output and command filter are accessed through the filter
screen.
Change/verify Velocity Loop parameters as needed.
Top speed limit. Max value may depend upon the back EMF & the Encoder value.
Min value: 0.
Maximum acceleration rate. Max value may depend upon load, inertia, & peak
current. Min value: 1. (Does not apply in position mode.)
Maximum deceleration rate. Max value may depend upon load, inertia, & peak
current. Min value: 1. (Does not apply in position mode.)
See Tracking Window Details (p. 92).
Velocity loop proportional gain. Range: 0 to 32,767.
Velocity loop integral gain. Range: 0 to 32,767.
Deceleration rate used by the velocity loop when the amplifier is hardware
disabled. Range: 0 to 100,000,000. Default: velocity loop Decel. Limit value.
For more information, see Velocity Loop Limits (p. 122).
Increases the resolution of the units used to express Vp and Vi, providing more
precise tuning. For more information, see Velocity Gains Shift (p. 123).
Decreases the resolution of the units used to express Vp and Vi, providing more
precise tuning. For more information, see Velocity Gains Shift (p. 123).
Vi Drain (integral
bleed)
Vi drain modifies the effect of velocity loop integral gain. The higher the Vi Drain
value, the faster the integral sum is lowered. Range: 0 to 32,000. Default: 0.
Click Close to close screen.